Sysbel WG7053F Emergency Stainless Steel Shower With Eyewash Basin Combination
1. Valve mechanism activates in one second or less; It stays open until manually closed.(Section 4.2,5.2,6.1.4,6,2)
2. Be connected to a system capable supplying adequate flushing fluid when all components are oprated simultaneously,(Section 4.5.5,7.4.4)
3. Height of the flushing fluid column pattem shall be between 82″(208.3cm) and 96″(243.8cm) above floor. (Section 4.1.3,4.5.4)
4. Watersupply shall be sufficient to supply at least 20GPM (75.7LPM) for 15 mimutes. (section 4.1.2,4.5.5)
5. Valve actuator shall be located not more than 175.3cm (69″) above floor. (section 4.2)
6. The diameter shall be minimum of 50.8cm (20″) at 152.4cm (60″) above floor. (section 4.1.4)
7. Center of the flushing fluid patterm shall be at least 16″(40.6cm) from any obstruction.(Section4.1.4,4.5.4)
8. Water flow pattren shall be positioned between 33″(83.8cm) and 53″(134.6cm) from the level on which user stands and 6″(15.3cm) minimum from the wall or nearest obstruction.(Section 5.4.4,6.4.4)
9. Deliverd at least 3.0 gallons(11.4liters) of water per minute for 15-minute (Section 6.1.6,6.4.5)
10. Construted of materials that will not corrode in the presence of the flushing fluid (Section 7.1.1,7.1.2,7.1.3)
11. Located 10 seconds or 55 feet from contaminants or hazardous materials, Locate on the same level as hazad and free of obstructions.(Section 7.4.2,B5)
12. Protect nozzle head from airborne contamination, dust covers shall be removed by water flow immedlately (Section 5.1.3,6.1.3)
13. Provided fushing fluid to both eye and face simultaneously at a velocity low enough without injury to skin (Section 5.1.1.6.1.1)